Not registered?
If you have not yet registered on the Valsir web site fill in the form with your details and obtain free access to the download area where you will be free to download our price lists and technical brochures. You will also have the possibility of receiving our periodic newsletter: the best way to remain up-to-date on all the latest developments in Valsir.
The heating and cooling system designed specifically for residential buildings and offices where the laying height is at least 72 mm.
V-ERRE system is the ideal solution in buildings where laying space is limited but we don’t want to forego the advantages of a Valsir floor heating and cooling system. The coupling of a rigid pocketed sheet with a molded polystyrene sheet allows the space occupied to be significantly reduced.
By using the V-Acustic multi-layer soundproof floor covering over screed of 100 kg/m2, performance improvements of 28 dB are achieved.
Noise reduction to impact sounds. (UNI EN 12354-2 - App. C2) ΔLW > 28 dB
Panel characteristics | Measurement unit | V-ERRE |
Resistance | - | Class 200 150 |
Surface type | - | Pre-formed |
Panel working dimensions | mm x mm | 1200x800 |
Minimum pipe spacing | mm | 50 |
Insulation thickness | mm | 10 - 20 - 30 |
Total thickness | mm | 32 - 42 - 52 |
Density | kg/m3 | 30 - 25 |
Compressive strength | kPa | 200 - 150 |
Flexural strength | kPa | 250 - 200 |
Fire resistance | - | Euroclass E |
Thermal conductivity | W/mK | 0,035 |
Thermal resistivity | m2K/W | 0,45 - 0,75 - 1,0 |
Valsir provides complete support both during the planning phase and on site, thanks to a first-class technical office made up of a team of highly experienced engineers, capable of dealing with the most complex system requirements.